Location:Home - Products
ABDT-GL5100 Series Single-loop Display Indicator
ABDT-GL5100 Series Single-loop Display Indicator with automatic SMD packaging technology, has a strong anti-jamming capability. Designed with dual-screen LED display, it could display more contents. It can be used in conjunction with various sensors、transmitters to display temperature, pressure, liquid level, speed, force and other physical parameters, and to output alarm control, analog transmission, RS-485/232 communication etc. More than the traditional digital display meters is a new function to restore the factory default parameters, with easier operation and better applicability.
Product Details
Overview
ABDT-GL5100 Series Single-loop Display Indicator with automatic SMD packaging technology, has a strong anti-jamming capability. Designed with dual-screen LED display, it could display more contents. It can be used in conjunction with various sensors、transmitters to display temperature, pressure, liquid level, speed, force and other physical parameters, and to output alarm control, analog transmission, RS-485/232 communication etc. More than the traditional digital display meters is a new function to restore the factory default parameters, with easier operation and better applicability.
Input | |||||
Input signals | Current | Voltage | Resistance | Thermocouple | |
Input Impedance | ≤250Ω | ≥500KΩ | |||
Maximum input current | ≤30mA | ||||
Maximum input voltage | ≤6V | ||||
Output | |||||
Output signals | Current | Voltage | Relay | 24V distribution or feeder | |
Output load capability | ≤500Ω | ≥250 KΩ (Note: Please replace the module for higher load capacity) | AC220V/0.6(small) DC24V/0.6A(small) AC220V/3A(big) DC24V/3A(big) According to Remarks | ≤30mA | |
Comprehensive parameter | |||||
Accuracy | 0.2%FS±1 bit | ||||
Setting model | Panel touch key parameter setting values locking; store the setting values permanently | ||||
Display style | -1999 ~ 9999 display range 0 ~ 100% measured value lightness bargraph display; LBD display for working state | ||||
Working environment | Ambient temperature: 0 ~ 50 ℃; Relative humidity: ≤ 85% RH; Far from strong corrosive gas | ||||
Power supply | AC 100 ~ 240V, (50/60HZ); DC 20 ~ 29V | ||||
Power | ≤5W | ||||
Frame | Standard snap-on | ||||
Communication | Standard MODBUS communication protocol, RS-485, communication distance up to 1 km, RS-232 ,communication distance up to 15 meters Note: While with communication function, the communication converter should be a active one. |
Note: The output load capacity of external dimensions D, E, Hinstrument relay is the AC220V/0.6A, DC24V/0.6A.
Instrument dimension and hole size:
Dimensions/code | Hole Size |
160*80mm (Horizontal )/A | 152*76mm |
80*160mm (Vertical )/B | 76*152mm |
96*96mm (squarely)/C | 92*92mm |
96*48mm (Horizontal)/D | 92*45mm |
48*96mm (Vertical)/E | 45*92mm |
72*72mm (squarely)/F | 68*68mm |
48*48mm (squarely)/H | 45*45mm |
160*80mm (Horizontal / beam)/K | 152*76mm |
80*160mm (Vertical / beam)/L | 76*152mm |
96*96mm (squarely)/M | 92*92mm |
2) Digital display
PV display window: show measured values; in parameter setting state, display parameter symbols
SV display window: show input dividing symbol, alarm values etc. as your choice; in the parameter setting state, display setting parameter values
3) Keys
4 Indicators
AL1: Alarm 1 indicator
AL2: Alarm 2 indicator
AL3: Alarm 3 indicator
AL4: Alarm 4 indicator